| product or component type |
Circuit breaker
|
|
|---|---|---|
| range of product |
I-Line
|
|
| Trip Unit Type |
Thermal-magnetic
|
|
| Rating Code |
A
|
| Line Rated Current |
40 A
|
|
|---|---|---|
| Number of Poles |
3P
|
|
| Interrupt Rating |
18 kA at 480 V AC
25 kA at 240 V AC 10 kA at 250 V DC |
|
| System Voltage |
250 V DC
480 V AC |
|
| mounting mode |
Unit mount
|
|
| electrical connection |
Lugs load
Lugs line |
|
| Wire Gauge |
AWG 14...AWG 1/0 (copper) 1 cable(s)
AWG 12...AWG 1/0 (aluminium) 1 cable(s) |
|
| Terminal Type |
AL100FA
|
|
| magnetic hold current |
400 A
|
|
| magnetic tripping current |
850 A
|
|
| phase connection |
ABC
|
|
| height |
6.4 in
|
|
| width |
4.5 in
|
|
| depth |
4.13 in
|
| product certifications |
UL listed
CSA |
|---|